Troubleshooting System Operation
JANOS is designed with the philosophy that the tools needed to understand and
diagnose system operation are an important part of the product itself. An
embedded controller should not become a black box when something goes wrong.
JANOS provides facilities for observing running processes, monitoring
application output, examining communications, capturing network traffic,
testing I/O, reviewing system activity and collecting diagnostic information.
These tools are intended to help isolate a problem while the system is
operating and, whenever practical, without disturbing that operation.
Automation systems typically operate as a chain of cause and effect. A digital
input may change state, or a command may arrive through a serial port or
network connection. That stimulus originates with an external system and
triggers built-in logic, a supplied application or a custom program. Decisions
are made and actions follow, perhaps changing relay states or transmitting
commands to another external system. When the expected result does not occur,
the problem may exist anywhere along this chain. The cause may be external to
the JNIOR, within its communications, logic or application processing, at its
outputs, or in the external system receiving the resulting action.
Effective troubleshooting means working along this chain to determine where
expected behavior breaks down. JANOS provides diagnostic tools that help
observe and verify each step, allowing the source of a problem to be isolated
rather than assumed. These tools can be invaluable in locating the root cause
even when the problem ultimately lies outside of the JNIOR.
APPROACHING THE PROBLEM
Begin by clearly defining the problem. What happened, and what should have
happened instead? What event or condition should have triggered the expected
action? Being able to state the problem in these terms provides a starting
point for troubleshooting and is also valuable information should you need to
contact
technical support
Consider what may have changed. Did the automation operate properly in the
past, or is this a new function that has not yet worked as expected? Look for
changes to the JNIOR, its configuration or applications, but also consider what
may have changed elsewhere in the system. Equipment, wiring, network
configuration, software and operating conditions outside of the JNIOR may all
affect behavior.
Next, identify the chain of events involved. Determine the source of the
triggering input and how it reaches the JNIOR. Identify the logic or
application that processes that input and makes the necessary decisions.
Finally, determine what output or communication should result and where it
goes. Each of these points can then be checked independently to determine where
actual behavior first differs from what is expected.
Timing may also be important. Note when the problem occurred and any external
conditions that existed at the time. Consider whether the system was actively
processing events or whether the problem appeared following a period of
inactivity. Logs and other timestamped events can be particularly valuable in
establishing the sequence of activity leading up to a problem and in
correlating JNIOR activity with events elsewhere in the system.
Make sure that the date and time on the JNIOR are correct. Much of the
diagnostic information maintained by JANOS is timestamped, and those times may
need to be correlated with logs or events from other equipment. Normally the
JNIOR uses NTP to maintain accurate time. An incorrect clock can make otherwise
useful diagnostic information difficult to correlate.
LOOKING FOR SYSTEM CHANGES
When an automation that previously operated correctly begins behaving
differently, first look for evidence that something in the system has changed.
JANOS maintains information that can help establish when configuration changes,
errors and other significant events occurred. Checking this information before
changing anything further may identify the cause directly or provide an
important point in time from which to investigate.
Syslog Events
The system log, stored in the
jniorsys.log file, records significant JANOS
activity and should be reviewed for events near the time the problem first
appeared. From the command line the following
CAT command can be used to
display recent log entries.
cat -p jniorsys.log
This content can also be viewed in the Syslog tab of the JNIOR WebUI. It may
even be searched by using
GREP,
EDIT or
MORE
In particular, look for configuration changes such as modifications to
Registry keys, as well as application, system and other events that might
correspond with the change in behavior.
Errors and Exceptions
The presence of an
errors.log file is also significant, but its timestamp may
be as important as its contents. Determine when the file was last written and
whether that time corresponds with the problem being investigated. If it does,
or if it has been written even more recently, examine the file for exceptions,
errors or other information that may identify what occurred.
When a file is modified its
Last Modification date is updated. This timestamp
may be viewed by listing the folder content using the
LS command as follows. If
you omit the file name the entire folder contents are listed by descending
modification date.
ls -lv errors.log
You may then use the
CAT command or editor features as mentioned above to examine
the
errors.log file content.
General Logging
You might also look for any application specific LOG files that may have been
updated around the time of the issue. Some applications keep additional
information in separate LOG files. While logs are generally written to the
root folder of the file system, there may be logs located in longer term storage.
You can use the
FIND command to look for those. For example:
find
.log
There are additional techniques for monitoring applications. Those are typically
not enabled by default, but can be activated. It becomes necessary to wait
for the next occurrence of the issue. These will be discussed in a subsequent section.
VERIFYING INPUT TRIGGERS
An automation sequence may be triggered by a change in a digital or analog
input, data received through a serial port, a command or message received over
the network, or an internally generated event such as a timer or scheduled
action. The trigger may originate directly from connected equipment or
indirectly from another controller, computer, application or network service.
The first step is to verify that the expected trigger actually reached the
JNIOR.
Confirming Digital Input Changes
If an action is triggered by a change of input state and the event did not
occur, then it is important to check if there was any input change. This can be
done using the
IOLOG command. For example:
iolog -o
The -O option here directs the output to the terminal for viewing. By default
the command copies the log to the
jniorio.log file. You may choose to do that
and then examine the file content with
CAT or the
ED editor.
The log details the state of inputs (DIN) and relay outputs (ROUT) and their
changes down to the millisecond. Here is a sample:
06/30/26 13:05:21.552, DIN ---- 0000 0000, RLY ---- ---- 0000 0000
06/30/26 13:07:09.908, DIN ---- 0000 0001, RLY ---- ---- 0000 0000
06/30/26 13:12:38.101, DIN ---- 0000 0000, RLY ---- ---- 0000 0000
06/30/26 13:17:39.072, DIN ---- 0000 0001, RLY ---- ---- 0000 0000
06/30/26 13:29:01.186, DIN ---- 0000 0000, RLY ---- ---- 0000 0000
If the desired action did not occur, check the IOLOG to determine if the input
state did change at that moment. If there was no I/O event then the problem is
likely external to the JNIOR. Either the remote signal was not sent or wiring
is no longer proper.
If the input signal did change but there wasn't the desired response, you will
need to look further down the chain.
If the action is triggered by some other means and the response is dependent on
input states, check to ensure that the inputs and the response are properly
correlated. Did the right input states generate the right response? You may
need to record the input status for use later in your diagnosis.
This also shows the relay output states. If the result of an automation action
is a change of relay status, you can see how the
IOLOG command can provide
confirmation of that as well.
It is possible to artificially generate events for testing purposes. This can
be a useful advanced debugging technique but should be approached with caution.
The JNIOR cannot determine the consequences of an automation action. Simulating
an input or forcing an output might activate equipment, trigger alarms or cause
other unexpected actions in connected systems. Such testing should only be
performed when the purpose of the I/O and the resulting automation actions are
fully understood.
Verifying Serial Triggers
External equipment may communicate with the JNIOR using a Serial connection.
This is typically RS-232. We highly recommend that this be achieved using the
AUX serial port. This is located at the top of the JNIOR to the right of the
power and
Sensor Port connectors.
The
COM (labelled RS-232) port provides access to the Command Line Interface
(CLI). During boot there are additional diagnostic messages transmitted through
this port. Both of these could interfere with the protocol that the remote
system is using. This could be the cause of some difficulty.
The AUX port supports additional communications features that are not available
on the COM port. One of those is the
Transmission Log. This is accessible using
the
IOLOG command as follows. Here the -A option selects the AUX log and the -O
option directs the output to the terminal screen.
iolog -ao
Characters (or bytes) passing through this port are logged. This command
displays that traffic. An example follows. Here you can determine if the remote
system is properly communicating and sending the correct messaging format.
-- 10/02/26 14:45:06.879
646.790
72 75 6E 20 72 65 73 65 74 5F 73 68 6F 77 0D 0A run reset_show..
-31--30--2F--30--32--2F--32--36--20--31--34--3A--34--35--3A--30- 10/02/26 14:45:0
-37--2E--35--34--31--20--2B--20--65--78--65--63--75--74--69--6E- 7.541 + executin
-67--5F--6D--61--63--72--6F--20--72--65--73--65--74--5F--73--68- g_macro reset_sh
-6F--77--0D--0A--31--30--2F--30--32--2F--32--36--20--31--34--3A- ow..10/02/26 14:
-34--35--3A--30--38--2E--35--37--36--20--2B--20--65--78--65--63- 45:08.576 + exec
-75--74--65--64--5F--6D--61--63--72--6F--20--72--65--73--65--74- uted_macro reset
-5F--73--68--6F--77--0D--0A-
show..
-- 10/02/26 14:45:55.518
46.917
72 75 6E 20 65 78 74 72 61 5F 70 61 75 73 65 0D run extra_pause.
0A -31--30--2F--30--32--2F--32--36--20--31--34--3A--34--35--3A- .10/02/26 14:45:
-35--36--2E--32--30--33--20--2B--20--65--78--65--63--75--74--69- 56.203 + executi
-6E--67--5F--6D--61--63--72--6F--20--65--78--74--72--61--5F--70- ng_macro extra_p
-61--75--73--65--0D--0A--31--30--2F--30--32--2F--32--36--20--31- ause..10/02/26 1
-34--3A--34--35--3A--35--37--2E--30--33--37--20--2B--20--65--78- 4:45:57.037 + ex
-65--63--75--74--65--64--5F--6D--61--63--72--6F--20--65--78--74- ecuted_macro ext
-72--61--5F--70--61--75--73--65--0D--0A- ra_pause..
If the outgoing characters display but those incoming are missing or
unintelligible, then a serial port parameter mismatch might be the cause. For
instance, both the JNIOR and the remote system must use the same Baud rates.
That would be a configuration setting in both cases.
Often a message must be precisely terminated with a CR ('\r' 0x0D), LF ('\n'
0x0A), or CRLF sequence of both. This is where you can see that detail and
confirm the termination used. This is a common concern in Digital Cinema.
Here we note that an automation action might also result in a message
transmitted by the AUX port. This port can be used to trigger events either
within the JNIOR or externally or both. The IOLOG command is therefore a useful
diagnostic tool in either case.
The AUX port can also be used in protocol conversion applications. Protocol
conversion is, after all, a type of automation.
Verifying Network Triggers
Often these days, the Local Area Network (LAN) plays a key role in equipment
communications. The JNIOR is a hardware I/O device with wired inputs and relay
outputs, yet it is not uncommon for it to serve in a network facing role.
Network messages can trigger events on the JNIOR and the JNIOR can drive other
devices through the network. This can include protocol conversion. The LAN can
be busy.
The
NETSTAT command displays the status of TCP/IP connections. This shows the
active servers on the JNIOR side as well as any remote connections in progress.
If the JNIOR is supposed to be connected to an external system pending a
trigger, that connection should be displayed in this list. You can confirm it
with NETSTAT.
The NETSTAT -M monitoring mode shows the current status and updates that every
couple of seconds. If an external device is supposed to connect to the JNIOR at
a certain time, you can watch it happen. If the automation is to make an
outward connection in response to a trigger, you can watch that happen as well.
Any keystroke exits the monitoring.
As an aside, the
THD,
CAT and
PS commands also support monitoring modes. Both
NETSTAT and PS allow the specification of up to 8 text files that can be
displayed along with the network or process status updates. This feature
performs the CAT function that lists additional lines added to the file in real
time. You can get creative in observing connections, processes and logging
simultaneously.
If an event in the past did not go as expected, the NETSTAT -P command and
related options can be used to display captured network traffic. JANOS supports
a network sniffer similar in function to Wireshark. In fact, the NETSTAT -C
command generates a
PCAPNG file in the
/temp folder. This can be downloaded. It
will open up in Wireshark if you have that installed on your PC.
Unlike Wireshark, JANOS continuously captures network traffic. The amount of
time captured depends on the defined size of the capture buffer. You can set
filters to reduce the capture traffic and to focus that on specific equipment.
You can also use filters to select what traffic is displayed or saved then from
the buffer into the
PCAPNG file.
This might allow you to confirm the communication that would have triggered an
event even if it is considerably in the past.
The NETSTAT -S command with associated options works just as the -P option.
This, however, will display network traffic in real time. This allows you to
watch events unfold.
VERIFYING RESULTING ACTIONS
Once the expected trigger has been confirmed, it is useful to next determine
whether the intended result occurred. There is generally no need to investigate
the internal processing if the JNIOR received the expected trigger and produced
the expected response. In that case, troubleshooting can continue beyond the
JNIOR with the external equipment or system that should have acted on that
response.
Many of the same diagnostic tools used to verify triggers can also confirm
resulting actions.
IOLOG can confirm relay output changes, the AUX transmission
log can verify serial messages sent to external equipment, and network
monitoring or packet capture can confirm communications transmitted over the
network.
DEBUGGING PROCESSING
If you have confirmed that the expected trigger reaches the JNIOR and either
there is no response, or the response is not that expected, the next step is to
determine how the trigger should have been processed. This requires identifying
the function or application responsible for processing the trigger and
verifying that it is properly configured and operating as expected.
Some actions can be accomplished using built-in capabilities. These would not
require an active application program. An example would be the change of relay
state in response to a JNIOR Protocol message. Both the JNIOR Protocol and the
JANOS Management Protocol
JMP are built-in functions that can control outputs.
These protocols can also report input status to remote systems. So logically a
protocol message might be sent in response to a trigger such as an input
change. In either case the operations are configured using Registry settings.
Searching Configuration
While an application might store configuration information in an INI file or
file with some other extension, most applications, especially those built-in
functions, keep their configuration in the Registry. The Registry contains
keys
which are named entries. Each of those has a
value. You can examine and alter
Registry settings using the REGISTRY or
REG command.
To support debugging like this, JANOS logs all Registry changes in the
jniorsys.log syslog file. You can search for recent Registry changes using the
following command: + cat jniorsys.log* | egrep "Removed|Added|Changed"
This command uses
CAT to access the content of the
jniorsys.log file. The '*'
wildcard causes CAT to include the content of
jniorsys.log.bak. We include that
because the LOG ages to BAK after a time and we look back further this way. The
'|' passes the output of that command to
EGREP which selects lines containing
"Removed", "Added", or "Changed". The uppercase characters are important
although you can include the -I option for a case-independent search.
Note that if your JNIOR runs JBAKUP, even older events will be stored in
/flash/baks/jniorsys.log.zip. Assuming that the issue at hand occurred
recently, looking back into ancient history may not be necessary. If you do
need to look further back, and JBAKUP is active, you can use the following.
cat /flash/baks/jniorsys.log/jniorsys.log.bak | egrep "Removed|Added|Changed"
This uses the fact that, in some cases, a ZIP library may be accessed as a
virtual folder. Here the CAT command reaches into that compressed library and
produces the content of the likely large
jniorsys.log.bak file stored in there.
If you suspect that a Registry key may have been changed, you can access a last
modification timestamp for the key. Here the REG command fetches that
information.
bruce_dev2 /> reg -m IO/Inputs/din1/Inversion
[2605041245] IO/Inputs/din1/Inversion = disabled
The timestamp here is in the format YYMMDDHHMM. On this
bruce_dev2 JNIOR a
search into the JBAKUP compressed library does reveal that change on that date.
Unfortunately, most users rely on the main administrator account login. So it
is not possible to say
who or
what made that change. Evidence of that might
appear in some other LOG file.
Relative to the issue at hand, look for configuration changes that might apply
to the source of the event trigger, the resulting action, and the protocol (or
application) that processes the trigger. For example, in a case using serial
communications the Baud rate may have changed. For protocols you need to ensure
that they are enabled and on the correct port. Both the JNIOR and the remote
system must agree on these things.
The entire Registry may be listed using the command:
reg . You may include the
-X option to display additional system keys that are defaulted. This output
might be piped into
GREP or EGREP as well. Alternatively, you may examine the
/flash/jnior.ini file. This contains a backup of the Registry. This file is
generated by the system and should not be externally modified. Make Registry
changes using the REG command.
There are many conditions that can, if changed, disrupt operation. Hopefully
something that has changed will suggest the cause.
Verifying Execution Status
Some operations require a running application. For example, the MODBUS protocol
is very popular with industrial controls. This protocol can be used to report
input status or to change relay states. It is available for both
client and
server roles. MODBUS is supplied with the JNIOR. That application must be
running.
An application is generally started at boot using a Registry
Run key. If the
application doesn't start, a missing or improper
Run key may be at fault. For a
situation that was working and recently encountered an issue, a
Run key change
should be apparent when searching for configuration changes. Applications can
properly start and then encounter a situation that might cause them to stop. In
this case some error or exception would be logged.
The
PS command can be used to determine if an application is running. This can
also tell you how the application was started. Note in the following that the
MODBUS Server is running as well as other applications. Other system processes
are indicated.
bruce_dev2 /> ps
0: Idle Process
1: Network Service
2: System
3: Run/dblogs
4: Run/flash/modbusserver.jar
5: Command/Serial
6: Secure Transport
7 total 8.989 uptime 44.8K free pram
This command was executed after this unit was up for only 9 seconds. Note that
pram refers to internal Processor RAM. This is a limited resource and the 44.8K
reports a normal amount. A more detailed (verbose) process status is available.
bruce_dev2 /> ps -v
runtime % mem msg hnd stk frm id desc
5:20.186 83 0: Idle Process
23.307 06 3023.1K 8 17 3 3: Run/dblogs
9.251 02 2.7K 8 27 2: System
3.073 00 489.1K 8 17 10 4: Run/flash/modbusserver.jar
1.244 00 16.1K 8 24 1: Network Service
0.117 00 64.3K 8 14 5: Command/Serial
6 total 6:21.290 uptime 77.9K free pram
Here we see that 6 minutes later, one process has terminated, the amount of
pram has increased, and MODBUS continues to run. Here we see how much CPU
activity is attributed to each process at that moment. We also see the amount
of standard memory that process has consumed. The other parameters are message,
handle, and frame counts. The
stk value is the largest percentage of process
stack required by the process (highwater mark).
Much larger memory usage on the order of MB, might indicate an application
problem. High message, handle or frame counts might also be an indication of an
issue. A highwater stack percentage over 80 should also be of concern.
Processes may routinely utilize nearly 100% of the CPU. That is normal. But
that condition must not persist indefinitely. In these cases it is best to
contact the author of the application about the concern. You can start by
contacting
INTEG support
When an Application Stops
If an application should be running but does not appear to be, there should be
some indication of what caused it to stop. Assuming that the Registry
Run key
looks proper and that the program (JAR) file is present in the
/flash folder,
the next step is to look for an
errors.log file.
Java applications encounter
exceptions and these often provide a short message
indicating the cause. This information will be sent to the
errors.log file.
Check for this file and its timestamp using the
LS -L folder listing command.
If the file is present, you may examine its content using
CAT
If you find something there that is not immediately obvious to you, please feel
free to contact INTEG for assistance.
GETTING BACK UP AND RUNNING
Often there is not time to debug. Especially if that process is foreign to you.
There is a tendency to
REBOOT and hope for the best. In fact, that is often
recommended by a lot of technical support people. If you need to get back up
and running, there is no problem in rebooting. Just understand that there is a
good chance of the problem occurring again.
Before rebooting or making changes, consider using the JNIOR Support Tool to
collect a snapshot of the system if circumstances permit. The snapshot
preserves diagnostic information and system status that may be useful later in
determining what occurred. This is particularly valuable when immediate
recovery is more important than investigating the problem while it is present.
We do not recommend, however, purposely establishing a reboot schedule. In an
analogy with aviation, the high risk operations are takeoff and landing. Those
are analogous to startup and shutdown. Both carry risk that operation will be
disrupted and may not return to normal.
JNIOR users tend to reboot the product by pulling power briefly. While we have
worked hard to prevent it, abruptly removing power stops transactions in
midstream. A partial memory write leaves the system in a corrupt state. This
may not be corrected at boot and lead to additional problems. You should use
the soft REBOOT command or perform the reboot through the Support Tool or other
protocol.
The JNIOR has been designed to run 24/7/365. In other words there is no real
need to start fresh. Not with any frequency.
PREPARING FOR RECURRENCE
Restoring normal operation does not necessarily mean that the cause of a
problem has been identified. If the problem is intermittent, it may be
necessary to wait for it to occur again before enough information can be
collected to determine the cause. JANOS provides several facilities that can be
enabled or prepared in advance to preserve additional evidence when that
happens.
Some of these facilities monitor activity and create additional logging. Others
establish a baseline that can later be used to determine what changed. The
appropriate approach depends on what is known about the problem and which parts
of the automation chain remain suspect.
Capturing Application Output
Sometimes we execute applications in the foreground from the command line. This
would allow us to observe debugging information as it is displayed by the
application. So applications have been developed to output such information.
When they are run in the background, this output is normally discarded.
An issue with this approach is that the application must be disturbed. It has
to be stopped and then started in a command console session. That session then
has to be monitored in order to catch the event as it occurs. This is not
convenient. The disruption of ongoing execution could also reset the cause and
not lead us to a solution.
JANOS v2.6 now allows us to collect application output in the background as
well. This can be enabled and disabled without disturbing the running
application. This is particularly useful when investigating intermittent
problems where restarting the application might alter or eliminate the
condition being investigated.
Applications may output information to the
stdout stream. In a console session
the
stdout stream is brought to the display. In the background it is usually
ignored. However, if the application sees an existing
stdout.log file in the
root directory, it will now append its output to that file.
Normally the
stdout.log file is not present. Output is discarded. We can create
the file using the
TOUCH command as follows: + touch stdout.log
Now the file exists. It will appear in the directory listing. And it will grow
as output from applications is collected. This is a LOG file and it will age to
a BAK file just as others do. But now we can monitor it selectively from the
command line using
CAT as follows:
cat -m stdout.log
This will display the last few lines that exist in the file and display any new
output as it occurs. Any keystroke interrupts this monitoring.
The captured output in
stdout.log can now be reviewed for clues surrounding the
next occurrence of the issue at hand. Some applications also log this debug
detail to their own LOG files. Sometimes those are stored in the
/flash folder.
Focusing on a Single Application
Multiple applications can be executing on a JNIOR. Each could be providing
debug output. All of it will be entangled in the
stdout.log file. In some cases
one application might overwhelm the others and mask needed debug output.
Fortunately, you can select the output for a single application. To do so, you
must name the LOG file using the program name. So for instance if the EKM.JAR
program is running and we want only that debug output, you would create the
file as shown here:
touch stdout-ekm.log
The program name is determined by what comes after the last '/' separator in
the process name shown by the
PS command. That name is placed after a dash in
the file name as can be seen above. If both files exist, output from that
application is directed to its application-specific file while output from
other applications continues to be collected in
stdout.log.
To stop capturing the debug output, simply remove the file(s) with the
RM command. You can also rename it with the
REN command if you want to save content
but stop capturing.
Note that capturing diagnostic output consumes root folder file space. It should
normally be disabled when it is no longer needed.
Preserving Network History
JANOS continuously captures network traffic in a ring buffer. When that buffer
becomes full, the oldest captured packets are discarded to make room for new
traffic. On a busy network this can significantly limit how far back you can
look after an intermittent problem occurs.
Capture filtering (see
filter) can be used to extend that history. Generally it
is better to exclude traffic known to be unimportant than to select only the
traffic that you expect to need. Unexpected network activity may itself provide
an important clue. For example, WebUI traffic can be excluded from the capture
with a filter such as:
netstat -f "!(80|443)"
This can be particularly important when investigating a problem through the
WebUI. Connecting to the JNIOR with a browser generates additional network
traffic. Without appropriate filtering, the act of investigating the problem
can consume capture space and discard some of the older traffic that you are
trying to examine.
The size of the network capture ring buffer can also be increased to retain
additional history. Increasing the buffer and eliminating unnecessary traffic
can substantially extend the period represented by the capture. The objective
is to preserve enough network activity before, during and after the next
occurrence to help establish what happened.
Enlarging the Buffer
The JNIOR by default allocates 512KB of memory for network capture. The NETSTAT
-C command is used to generate a PCAPNG capture file which can be downloaded
and opened with the Wireshark network protocol analyzer
(!https://www.wireshark.org!wireshark.org). The default 512KB can represent
minutes or even hours of network operation depending on the amount of network
use. This packet buffer can be increased using this Registry key and can be set
for any number of KB between 512 and 8192 (8MB Maximum).
reg IpConfig/CaptureBuffer = 8192
An extremely large PCAPNG file can be difficult to upload and process. The
NETSTAT -C command can also include a capture filter, writing only those
packets of interest to the capture file.
RECOMMENDATIONS
If you encounter a problem, rebooting may get you back up and running. We
suggest that you make note of the event and let INTEG know about it. We do not
accept there being any level of background annoyance. While that might be
normal for some other devices, it is unacceptable for JNIOR.
To be proactive, please update your Series 4 JNIORs to the latest JANOS
release. As of this writing JANOS v2.6 is current. We all avoid updates having
been burnt by those at one time or another. A JANOS update should not be
considered in that category of risk. These updates predominantly correct issues
that have been identified. Those may not have affected you. But there is a
chance that they actually have. And, you may not have noticed. Or, that they
will in the future. Please install the update or run the Support Tool Update
Project. If you are uncomfortable with that process,
INTEG Support will be
happy to walk you through it.
SERIES 3 JNIOR
As of this writing there are 25 year-old Series 3 JNIORs in operation. This
product line has been a workhorse. The hardware does decay with time. The Flash
memory components have a wear factor and will eventually fail. Batteries that
retain LOG information and configuration go dead. Those cannot be easily
changed on the Series 3.
We cannot support the Series 3 at the level that we do with the current models.
The debugging tools are just not there. Much of what you have read in this
section of the manual pertains only to the Series 4 JNIOR. JANOS cannot run on
the Series 3. In fact, the operating system those units run is completely
unsupported by the original manufacturer. We can only work around that. We have
pushed that approach to the limit.
We recommend that you replace the Series 3 JNIOR with the corresponding Series
4. The Model 410 drops in for the Model 310 for example. All of the
applications are available for the Series 4 that were available before. There
is so much more performance and capability now.
INTEG Support will be happy
to work with you on the upgrade. We do not want you to struggle with older
equipment. Especially when we are not in a position to support you as we would
like.