IO/Outputs/[ROUT]/InitialState Registry Key
NAME
IO/Outputs/[ROUT]/InitialState
DEFAULT
undefined
DESCRIPTION
This key is used to define the initial behavior of relay outputs on boot.
The value defines a pulse duration in milliseconds where an entry of 0
indicates infinity. Setting the key to a value of 0 would effectively
close the output. Setting the key to a positive integer would cause the
output to pulse for the duration defined by the value An undefined or
negative value (default) results in no action.
NOTES
On power up all relays are in the inactive state. By default that is the
OPEN state where the contacts are not conducting. These are Normally Open
(NO) contacts. Depending on the model certain relays may be reconfigured by
internal jumper to be Normally Closed (NC). These would be conducting after
boot. Consider this option if you need a relay to conduct when the JNIOR
is powered down or after it reboots.
[/flash/manpages/registry.hlp:3507]